Parameter
Beschreibung
Values
Default
x1a in
Measured value correction Inp_a, P1 input value
Real
0
x1aOut
Measured value correction Inp_a, P1 output value
0
x2a in
Measured value correction Inp_a, P2 input value
100
x2aOut
Measured value correction Inp_a, P2 output value
100
x1b in
Measured value correction Inp_b, P1 input value
0
x1bOut
Measured value correction Inp_b, P1 output value
0
x2b in
Measured value correction Inp_b, P2 input value
100
x2bOut
Measured value correction Inp_b, P2 output value
100
Configuration
Description
Values
Default
Typ_a
Typ_b
Type L -200...900 °C
00
30
Type J -200...900 °C
01
Type K -200...1350 °C
02
Type N -200...1300 °C
03
Type S -50...1760 °C
04
Type R -50...1760 °C
05
Type T -200...400 °C
06
Type W(C) 0...2300 °C
07
Type E -200...900 °C
08
Type B 0...1820 °C
09
Type D 0...2300 °C
10
Voltage 0...30mV
27
Voltage 0...100mV
28
Voltage 0...300mV
29
Standard signal 0...20mA
30
Standard signal 4...20mA
31
Fail_a
Fail_b
Switched off
0
1
Upscale, Inp_a (Inp_b) = x100_a (x100_b)
1
Downscale, Inp_a (Inp_b) = x0_a (x0_b)
2
Substitute value, Inp_a (Inp_b) = XaFail (XbFail)
3
Xakorr
Xbkorr
Measured value correction Inp_a (b) switched off
0
0
Measured value correction Inp_a (b) effective
1
Unit_a
Unit_b
Unit of the measured value of Inp_a (b) = °C
1
1
Unit of the measured value of Inp_a (b) = °F
2
STK_a
STK_b
Internal temperature compensation
1
1
External temperature compensation
2
x0_a
(
b
)
Physical value Inp_a (Inp_b) at 0%
Real
0
x100_a
(
b
)
Physical value Inp_a (Inp_b) at 100%
Real
100
Xa
(
b
)
Fail
Physical value Inp_a (Inp_b) at 0%
Real
0
Tfm_a
(
b
)
Filter time constant of _a (Inp_b) in seconds
Real
0,5
Tkrefa
(
b
)
Reference temperature for Inp_a(b) at STK_a(b)
Real
0
Modular I/O - extension-modules
TC_INP (analog input card TC, mV, mA)
TC_INP (analog input card TC, mV, mA)
228
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...