Change mode (ramp/step)
If the set-point shall change in a step or ramp is deter-
mined by a parameter (
Wmode
) valid for all segments of a
recipe (default: ramp).
Ramp: The set-point changes linearly from the start (end
value of previous segment) to the end value of the relevant
segment in time
Tp
. For the first segment, the following
gradient is applicable: (
Wp1
-
Wp0
) /
Tp1
Step: The set-point goes to value
Wp
immediately at seg-
ment start and maintains it during segment time
Tp
.
Operation preparation and end position
Each program starts at an initial position
Wp0
, which is used and maintained with reset or first programmer set-up.
With program start from rest position, the first programmer segment runs from the instantaneous process value at the
time of start command („ramp“ with gradient (Wp1 - Wp0) / Tp1). With step change mode, the set-point of the first
segment is activated immediately.
At program end, either
w
the set-point of the last segment is maintained (
r
see below ),
w
or the programmer goes to rest position
Wp0
(
r
see below ) dependent of configuration (
PEnd
). The
program can be started either by entry of run (control input switch-on or off or front-panel operation) or
preset.
Programmer
9499 040 50611
APROG ( analog programmer ) / APROGD ( APROG data )
148
Tp3
Wp3
Wp2
Wp3
Wp2
Segment 3
Start
End
Tp2
Tp4
Ramp
Step
Segment parameters
Wp0
Wp1
Wp2
Wp3
Wp4
Wp5
...
Tp1
Tp2
Tp3
Tp4
Tp5
...
Preparation for
operation
elapsed
program time
Program
START
Program
END
Time
Wp0
Operation
RESET
Process value x
RESET
PRESET
PRESET
Profile with stop at end position
Profile with automatic reset at program end
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...