Analog programmer operating page
Analog programmer APROG has an operating page, which can be se-
lected in the operating page menu with input ‘
hide
‘ not connected.
To change the value of an input field, mark this value by means of
ID
(inverse display). When acknowledging the value with
M
, it
starts blinking and can be adjusted with
ID
. If the required value
was reached, acknowledge it with
M
.
If the FB inputs (function block inputs) allocated to the input fields in
the following table are assigned to the engineering, operation (change)
of this input field is not possible.
Input field
Operation
Display
FB input
Rec
If input ProgNo is wired, entering of the desired
recipe number is not possible over the frontside!
indicates the actual recipe number.
ProgNo
Seg
If control input preset is wired, entering the desired
segmentnumber is not possible over the frontside!
indicates the actual segment number
preset
Ü
No operation possible
start and end value of the actual
segment
*
No operation possible
display of actual set-point (
Wp
)
tNetto
Entry of required programmer time (preset to
time)
indicates the
run
time total
(without pause)
preset
tRest
No operation possible
indicates the time until program end
Status
stop
Stop the programmer
programmer stopped
run
run
Start the programmer
the programmer was started
reset
The programmer is switched to segment 0
and’
stop
‘
the programmer is switched to
segment 0 and’
stop
‘
reset
quit
Leave the field without change
progr
am
direct adjustment of segment parameters
segmentparameter
Extended programmer functions
Valid from :
SIM/KS 98
version 2.1
ET/KS 98
version 2.2
Set-point limits and decimal point (only APROG)
Parameter Description
Range
Default
W0
Lower input limits for Wp0 ... Wpn
-29999 ... 999 999
0
W100
Upper input limits for Wp0 ... Wpn
-29999 ... 999 999
100
Dp
Number of digits behind the decimal point with input and display of segment
parameters
0 ... 3
0
+
Note: When adjusting the segment parameters via the parameter level, these parameters are not effective!
Programmer
9499 040 50611
APROG ( analog programmer ) / APROGD ( APROG data )
150
Ü *
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...