24.6
Controller behaviour
Signaller, 1 output (not available with PIDMA):
The signaller is suitable for processes with small T
u
and low v
max
.
The advantage is in the low switching frequency. Switch-on is always at a fixed value below the set-point, switch-off is
always at a fixed value above the set-point.
The control variable oscillation band is determined as a result of :
X
x
T
T
X
v
T
X
u
g
Sd
u
Sd
0
=
· +
=
· +
max
max
The signal function corresponds to limit signalling, whereby the set-point is the limit value. The trigger point is symmet-
rical to the set-point; hysteresis X
sd1
is adjustable.
Output Y1
Configuration Effective controller parameters of a signaller with one output
CFunc
=
signaller,
1 output
W0
1)
Lower set-point limit for Weff
-29 999 ...999 999
W100
1)
Upper set-point limit for Weff
-29 999 ...999 999
W2
1)
Additional set-point
-29 999 ...999 999
Grw+
2)
Set-point gradient plus
off / 0,001 ... 999 999
Grw-
2)
Set-point gradient minus
off / 0,001 ... 999 999
Grw2
2)
Set-point gradient for W2
off / 0,001 ... 999 999
N0
Zero offset (only effective with
CType
=ratio controller)
-29 999 ... 999 999
a
Factor a (only effective with
CType
=3-element control)
-9,99 ... 99,99
Xsd1
1)
Signaller switching difference
0,1 … 999 999
Titel
Title of controller page (only display)
16 characters
Einh.X
Process value unit (only display)
6 Zeichen
W int
Internal set-point after transmission of the engineering to KS98
-29 999 ...999 999
1)
The values are specified in the process value unit
- e.g. [°C, °F, bar, %, etc.]
2)
The rate of change must be specified in units /minute (e.g. °C/min).
r
see gradient control page 192.
9499 040 50611
Controller
167
Controller behaviour
100%
0%
Y1
Â
Xn100
Xn0
W0
Weff
W100
Xeff
Xsd1
Static operating principle
of the signalling function
of a signaller, 1 output
Set-point
process value
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...