18.2
L1WRIT ( write level1 data )
General
This function is used to provide a data set transmitted by the interface to the engineering. The digital interface de-
scribes EEPROM cells with codes 31...39, function number 0. The data set comprises 8 analog process values (y1...y8)
and 15 digital control informations (z1...z15), which are provided to the engineering.
g
The transmitted data are stored in the EEPROM. After power failure, start is with the data rather than
with the default values.
Inputs/outputs
Digital outputs:
z1
...
z12
Digital process values, which can be written via the interface (default = 0)
Analog outputs:
y1
...
y8
Analog process values, which can be written via the interface (default = 0)
Engineering example
In the following example, the L1WRIT function block is used to make several process data (process values x2, x3, exter-
nal set-point and two alarm limits) and the control information (automatic/manual, w/W2, Wint/Wext and y/Y2) avail-
able to the engineering. These data can be written in a message via interface.
Communication
9499 040 50611
L1WRIT ( write level1 data )
114
Code 31
Code 32
Code 33
Code 34
Code 35
Code 36
Code 37
Code 38
Code 39
EEPROM
9 8 7 6 5 4 3 2 1 0
4 3 2 1 0
z1
z15
...
y1
.
.
.
.
.
.
.
y8
Interface
Example for L1WRIT engineering
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...