Text display and entry
Changing the texts displayed in the unit is possible only in the engineering tool!
Max. 16 characters can be entered into each text parameter.
The following values or texts are displayed:
Ü
Block number 3 digits
*
Fixed text or spaces (no access)
Ö
The first 16 characters of ‘Title’
ä
X 100
#
X 0
<
Last stored value
>
Unit for x1 (first 6 characters of ‘Unit’)
y
-100 *
Sample
,
Unit
VTREND operating page
VPARA has an operating page, which can be selected in the operating page menu with
input ‘
hide
‘ not used. VTREND has no operating functions. The operating page is
used exclusively for trend data display
Examples: Trend recording with 2 curves
Although distinction of different curves is not possible,
display of two values on a trend page may be purposeful
(e.g. controller set-point and process value, or one value and
zero, in order to have a curve). In the example, a clock
triggering switch-over between the values together with the
SELV1 is generated by means of a pulse.
For making a record at intervals of a second e.g.
in VTREND,
Unit
is set to s and
Sample
is set to 1.
Settings: Unit = s and
Sample =1
=
1/s = 3600/h
x0=0,
x100
and pulse/h to 3600,
1/2 sample interval = 1800 must be applied
to pulse input x1.
Cascading
Trend or data recording with any number of values can be realized by cascading VTREND function blocks. Limiting re-
fers only to the number of available block numbers and to the calculation time. The data sequence is dependent of
VTREND function block wiring.
Visualization
9499 040 50611
VTREND ( trend display )
112
:
Ü *
Ö
ä
<
y
#
>
Trend curve
Value x ... x-100
Value x-101 ... x-200
the earliest 100
stored values
Example of trend-/datarecording with n-values
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...