Configuration
Description
Values
Default
Type
Type L -200...900 °C
Type L
Type J -200...900 °C
Type J
Type K -200...1350 °C
Type K
Type N -200...1300 °C
Type N
Type S -50...1760 °C
Type S
Type R -50...1760 °C
Type R
Type T -200...400 °C
Type T
Type W 0...2300 °C
Type W
Type E -200...900 °C
Type E
Type B 0...1820 °C
Type B
Pt 100 -99,9...850,0 °C
Pt100 850
Pt 100 -99,9...250,0 °C
Pt100 250
2x Pt 100 -99,9...850 °C
2Pt100 85
2x Pt 100 -99,9...250,0 °C
2Pt100 25
0...20 mA
0...20mA
t
4...20 mA
4...20mA
0...10 V
0...10V
2...10 V
2...10V
Transducer 0...500
[
Pot.trans
Resistance 0...500
[
linear
0..500Ohm
Resistance 0...250
[
linear
0..250Ohm
Fail
Fail function off
disabled
Digital output
fail
= 1,
y1
=
x100
Upscale
t
Digital output
fail
= 1,
y1
=
x0
Downscale
Digital output
fail
= 1,
y1
=
XFail
Subst.val.
Xkorr
Measured value correction off
off
t
Measured value correction
adjustable
on
Unit
Unit = °C
only effective with thermocouple
and Pt100 setting
°
C
t
Unit = °F
°
F
STK
Internal temperature compens.
only effective with thermocouple
int.CJC
t
External temperature compens.
ext.CJC
x0
Physical value at 0%
only effective with standard
signals (0/4..20mA or 0/2..10V)
-29999 ... 999 999
0
x100
Physical value at 100%
-29999 ... 999 999
100
XFail
Substitute value with sensor error
-29999 ... 999 999
0
Tfm
Filtertime constant
[
s
]
0 ... 999 999
0,5
Tkref
Reference temperature at
STK
=
ext.TK
0 ... 140
0
Measured value conditioning
Before the pre-filtered (time constant ...; limiting frequency ...) analog
input signals are available as digitized measurement values with
physical quantiy, they are subjected to extensive measured value
conditioning.
Input circuit monitor
q
Thermocouples
The input circuit monitor monitors the thermocouple
for break and polarity error. An error is determined if the measured thermovoltage signals a
value which is by more than 30 K below the span start.
q
Pt100 measurements and transducers
are monitored for break and short-circuit.
q
Current and voltage signals
With current (0/4...20mA) and voltage signals (0/2...10V), monitoring for out-of-range (I >
21,5 mA or U > 10,75 V) and for short circuit
(I < 2 mA or U < 1 V) with “life zero” signals is provided.
Sensor errors are output as digital output (
fail
). In case of error, statuses ‘
Upscale
‘, ‘
Downscale
‘ or
‘
Subst.val.
‘ defined in the configuration can be preset for the input circuit.
Inputs
9499 040 50611
AINP1 ( analog input 1)
204
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...