21.1
C_KS8x (KS 800 and KS 816 node function - no. 58)
Node function
C_KS8x
provides the interface to one of the multi-channel temperature controllers KS 800 or KS 816.
Analog outputs
C1
…
C16
can be used to connect the
KS8x
functions, which represent each a controller of KS
800 (max. 8 controllers) or of KS 816 (max. 16 controllers).
Unlike the other KS98 functions, only one data function can be soft-wired to each analog o
utput.
Prerequisite for communication of KS98+ multi-function unit and KS800 or KS816 is the complying adjustment of the
CAN parameters. (
r
see *1)).
Outputs
Analog inputs
C1...C16
Connection of the KS8x functions (single controllers in KS800 / KS816)
Digital outputs
et-err
0 = no engineering error
1 = engineering error (different node function at the same KS800)
id-err
0 = correct node
1 = faulty node Id (no KS800 / KS816 replied under the configured
node ID)
valid
0 = no data
1 = data were received
online
0 = KS800/816 is off-line
1 = KS800/816 is on-line
fail 1
0 = no fail at do1...do12
1 = fail at do1...do12
fail 2
0 = no fail at do13...do16
1 = fail at do13...do16
fail 3
0 = no heating current short circuit
1 = heating current short circuit
di1
di1status
di2
di2 status
di3
di3 status
di4
di4 status
Parameter und Konfigurationsdaten
Configuration
Description
Range
Default
NodeId
KS800/KS816 node address
2...42
2
a
The data from the various controllers are read cyclically.
Maximally at intervals of 1.6 seconds (KS800) or 3.2 seconds (KS816), all data are updated.
*
1) The parameters for the CANopen bus are adjustable in engineering tool window "CANparameter” or via the
instrument parameters on the front panel (ET98
r
Device
r
CANparameter).
Connection of KS 800 and KS 816
C_KS8x (KS 800 and KS 816 node function - no. 58)
C_KS8x (KS 800 and KS 816 node function - no. 58)
134
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...