23.2
DPROG ( digital programmer ) / DPROGD ( DPROG data )
General
A digital programmer comprises a programmer (DPROG) and at least one data block (DPROD), whereby output
DBlock
of DPROGD is connected with input
DBlock
of the DPROG. Connection of several of these cascadable
functions (each with 10 segments) permits realization of a programmer with any number of recipes and any number of
segments. Limiting is only in the number of available block numbers and calculation time.
The data block has an analog output, at which it provides its own block number. This information is read-in by the pro-
grammer and used for segment data addressing. When an error in the segment data addresses is found, the reset value
is output (status display on operating page:
Error
‘).
After an engineering download,
Seg 0
is output (reset). If
run
is not connected,
stop
is used.
Programmer
9499 040 50611
DPROG ( digital programmer ) / DPROGD ( DPROG data )
152
PSet
DBlock
ProgNo
hide
lock
run
reset
preset
run
reset
end
fkey
do1
...
do6
TNetto
TBrutt
TRest
SegNo
ProgNo
D
PwrUp
PMode
Turbo
PEnd
DPROG
DPROGD
A
A
D
D1
D2
D10
...
t
Tp1 Tp2
Tp10
...
(32)
(16)
(8)
(4)
(2)
(1)
do6
do5
do4
do3
do2
do1
DBlock
DBlock
elapsed
program time
START
END
1
2
3
4
5
6
7
8
9
10
PRESET
to time
RESET
PRESET
to segment
t
Control output 1 (do1)
Control output 2 (do2)
Control output 3 (do3)
Control output 4 (do4)
Control output 5 (do5)
Control output 6 (do6)
Digital programmer definition
Summary of Contents for KS 98
Page 8: ...Description 9499 040 50611 Construction 8...
Page 10: ...Important technical data 9499 040 50611 Further external in and outputs 10...
Page 12: ...Versions 9499 040 50611 I O modules for units with modular option c basic card 12...
Page 14: ...Front view 9499 040 50611 14...
Page 16: ...Mounting 9499 040 50611 16...
Page 26: ...Maintenance 9499 040 50611 Further information 26...
Page 36: ...Scaling and calculating functions 9499 040 50611 LG10 10s logarithm 36...
Page 74: ...Signal converters 9499 040 50611 MEAN mean value formation 74...
Page 128: ...KS98 I O extensions with CANopen 9499 040 50611 RM_DMS strain gauge module 128...
Page 132: ...CSEND Send mod blockno s 21 23 25 27 No 57 132...
Page 140: ...Description of KS98 CAN bus extension 9499 040 50611 140...
Page 202: ...Controller 9499 040 50611 Process value calculation 202...