Parker EME
Introduction
192-120101 N11 C3I11T11 November 2007
15
1.6
Conditions of utilization
In this chapter you can read about:
Conditions of utilization for CE-conform operation ............................................................................15
Conditions of utilization for UL certification Compax3S .....................................................................18
Current on the mains PE (leakage current) .......................................................................................19
Supply networks ................................................................................................................................20
1.6.1.
Conditions of utilization for CE-conform operation
- Industry and trade -
The EC guidelines for electromagnetic compatibility 2006/95/EC and for electrical
operating devices for utilization within certain voltage limits 2004/108/EC are
fulfilled when the following boundary conditions are observed:
Operation of the devices only in the condition in which they were delivered,
i.e. with all housing panels.
In order to ensure contact protection, all mating plugs must be present on the
device connections even if they are not wired.
A mains filter is required in the mains input line if the motor cable exceeds a certain
length. Filtering can be provided centrally at the plant mains input or separately at
the mains input to each device or with C3M for each axis combination.
Devices in a commercial and residential area (limit values of Class C2 in
accordance with EN 61800-3)
The following mains filters are available for independent utilization:
Device: Compax3
Order No.:
Condition:
S0xxV2
NFI01/01
Only for motor lines > 10m
S1xxV2,
S0xxV4, S150V4
NFI01/02
Only for motor lines > 10m
S300V4 NFI01/03
independent
of the length of the
motor cable (always required)
Device: Compax3
Order No.:
Condition:
H050V4
NFI02/01
Only for motor lines > 10m
H090V4
NFI02/02
Only for motor lines > 10m
H1xxV4
NFI02/03
Only for motor lines > 10m
Industrial area (limit values class C3 in accordance with EN 61800-3)
Longer motor cable lengths are possible in industrial areas.
Devices in the industrial area (limit values class C3 in accordance with EN
61800-3)
The following mains filters are available for independent utilization:
Device: Compax3
Order No.:
Condition:
MP10
NFI03/01
Reference axis combination 6x10m
MP10
NFI03/02
Reference axis combination 6x50m
Connection length: Connection between mains filter and device:
unshielded: <
0.5m
shielded:
< 5m (fully shielded on ground – e.g. ground of control cabinet)
Mains filter: