Verify a DIMM
faults/0 | |
/SP/faultmgmt/0/ | timestamp | Mar 18 16:02:56
faults/0 | |
If this command reports a fault with a UUID go to
. If
show faulty
does
not
report a
fault with a UUID, you are done with the verification process.
6.
Switch to the system console and type the
fmadm repair
command with the UUID.
Use the same UUID that was displayed from the output of the Oracle ILOM
show faulty
command. For example, type:
#
fmadm repair 7c7efb20-3333-e2d7-b8ea-986b3e9dbaa9
Related Information
■
“Understanding DIMM Layout and Population Rules” on page 160
■
“Locate a Faulty DIMM” on page 161
■