Install the PDB
Install the PDB
Installing the PDB is a cold-service operation. You must power off the server before installing
the PDB.
1.
Position the PDB to where it installs into the server.
The bus bars are forward and down.
2.
Grasp the two motherboard handles, and slide the motherboard onto the
alignment pins.
See
“Servicing the Motherboard” on page 225
for cautions. For this service procedure, you
are not removing the motherboard. You are moving it slightly so that you can remove the PDB.
3.
Carefully insert the LED into the hole at the rear of the chassis.
4.
Place the bus bars into the channels, and align the PDB with two posts for the
captive screws.
146
Netra SPARC S7-2 Server Service Manual • February 2017
Summary of Contents for Netra SPARC S7-2
Page 1: ...Netra SPARC S7 2 Server Service Manual Part No E73207 03 February 2017 ...
Page 2: ......
Page 12: ...12 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 24: ...24 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 42: ...Server Fault Remind Button Operation 42 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 84: ...84 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 108: ...108 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 140: ...140 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 150: ...150 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 158: ...158 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 192: ...192 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 216: ...216 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 258: ...258 Netra SPARC S7 2 Server Service Manual February 2017 ...