Remove the Cable Management Arm
and D. You must disconnect the CMA connectors in reverse order, that is, disconnect connector
D first, then C, then B, and finally A.
Throughout this procedure, after you disconnect any of the CMA's four connectors, do not
allow the CMA to hang on its own weight.
Note -
References to “left” or “right” in this procedure assume that you are facing the back of
the rack.
1.
To prevent the rack from tipping forward when the server is extended, extend all
rack anti-tilt devices.
Caution -
To reduce the risk of personal injury, stabilize the rack cabinet and extend all anti-tilt
devices before extending the server from the rack.
For instructions for stabilizing the rack, see
.
2.
To make it easier to remove the CMA, extend the server approximately 13 cm (5
inches) out of the front of the rack.
3.
Remove the cables from the CMA.
a.
Disconnect all cables from the rear of the server.
b.
If applicable, remove any additional Velcro straps that were installed to
bundle the cables.
c.
Unwrap the six Velcro straps that are securing the cables.
d.
Open the three cable covers to the fully opened position.
e.
Remove the cables from the CMA and set them aside.
4.
Disconnect connector D.
a.
Press the green release tab (callout 1) on the slide-rail latching bracket
toward the left and slide the connector D out of the left slide-rail (frames 1
and 2).
When you slide connector D out of the left slide-rail, the slide-rail latching bracket portion
of the connector remains in place. You will disconnect it in the next step.
Preparing for Service
59
Summary of Contents for Netra SPARC S7-2
Page 1: ...Netra SPARC S7 2 Server Service Manual Part No E73207 03 February 2017 ...
Page 2: ......
Page 12: ...12 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 24: ...24 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 42: ...Server Fault Remind Button Operation 42 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 84: ...84 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 108: ...108 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 140: ...140 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 150: ...150 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 158: ...158 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 192: ...192 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 216: ...216 Netra SPARC S7 2 Server Service Manual February 2017 ...
Page 258: ...258 Netra SPARC S7 2 Server Service Manual February 2017 ...