4
Replace the complete Fan Unit.
1
3
2
1) Push the lever
1
to unlock the Fan Unit.
2) Lift the lever to tilt
2
the Fan Unit.
3) Remove
3
the complete Fan Unit.
5
Insert the new Fan Unit in the Box PC.
Ensure the end of the Fan Unit
A
is positioned under the fan guide
B
.
B
A
6
Connect the Fan Connectors to the board.
7
Mount the Cover.
8
Power ON the system.
Confirm both fans rotate immediately after Power ON.
The fans are replaced and the alarm is automatically reset.
7 Maintenance
7-8
NY-series Industrial Box PC Hardware User's Manual (W553)
Summary of Contents for SYSMAC NY Series
Page 4: ...Introduction 2 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 10: ...Index CONTENTS 8 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 32: ...Revision History 30 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 74: ...3 Hardware 3 32 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 114: ...4 Specifications 4 40 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 168: ...5 Installation 5 54 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 198: ...7 Maintenance 7 24 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 254: ...Appendices A 56 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 255: ...I Index I 1 NY series Industrial Box PC Hardware User s Manual W553 I ...
Page 258: ...Index I 4 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 259: ......