• The default
Input sensitivity setting
is
Standard voltage sensitivity
and this is correct.
Do not set this parameter to
Low voltage sensitivity
. Doing so can cause a system malfunc-
tion when switching to battery mode.
• The UPS Setting Utility can not be used when the Power Attendant Lite Utility is active.
To use the UPS Setting Utility:
1. Right-click the Power Attendant Lite Utility icon and select Agent Stop.
2. Use the UPS Setting Utility.
3. Right-click the Power Attendant Lite Utility icon and select Agent Start.
5-8-2
Connect UPS Using the I/O Connector
The I/O connector of the Industrial Box PC:
• receives the power status of the UPS with the UPS Mode Input when the Box PC has a Windows
operating system. For other operating systems this input is not functional.
• indicates the power status of the Box PC to the UPS with the Power Status Output.
Additional Information
• A UPS connection using the I/O connector is only possible for a Box PC with a Windows op-
erating system. For all other operating systems use the USB connector to connect the UPS.
Refer to
5-8-1 Connect UPS Using the USB Connector
on page 5-48 for details.
• The Box PC does not react automatically to the UPS Mode Input.
A custom software program is required
to shut down the Box PC when needed.
UPS Drivers and the required software is available.
• For Box PCs with Windows 10 or Windows 7 preinstalled:
• Drivers for the S8BA UPS are pre-installed
• Installation files and manual for the UPS Settings Utility are availabe in the installer directory
D:\OMRON-NY\Installers\UPS Settings Utility
• For all other Box PCs following software can be downloaded:
• Drivers for the S8BA UPS from this OMRON website.
• Installation files and manual for the UPS Settings Utility (Windows only) from this OMRON web-
Precautions for Safe Use
• Always use the recommended uninterruptible power supply (UPS) to prevent data loss and
other system file integrity issues caused by unexpected power interruption.
• Use an Omron S8BA UPS with the correct revision number to prevent improper system shut-
down.
• Correctly perform wiring and setting, and ensure that the shutdown by the UPS can be exe-
cuted.
Follow the steps below to connect the S8BA UPS to the I/O connector of the Box PC and to configure
it correctly.
Refer to
on page 5-36 for I/O Connector details.
1
Ensure the revision number of the UPS is correct.
Refer to
on page 3-31 for more information.
5 Installation
5-50
NY-series Industrial Box PC Hardware User's Manual (W553)
Summary of Contents for SYSMAC NY Series
Page 4: ...Introduction 2 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 10: ...Index CONTENTS 8 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 32: ...Revision History 30 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 74: ...3 Hardware 3 32 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 114: ...4 Specifications 4 40 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 168: ...5 Installation 5 54 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 198: ...7 Maintenance 7 24 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 254: ...Appendices A 56 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 255: ...I Index I 1 NY series Industrial Box PC Hardware User s Manual W553 I ...
Page 258: ...Index I 4 NY series Industrial Box PC Hardware User s Manual W553 ...
Page 259: ......