8 - 69
8 Pulse Output Units
NX-series Position Interface Units User’s Manual (W524)
8-
10 Fu
nct
ions
8
8-1
0-8 Inter
polation
Contro
l for
Missing Synchronization
Command
The Pulse Output Unit outputs pulses in sync with the command position that is received each fixed
period.
If synchronized communications falls out of sync or if the cycle is broken for any other reason and a
command is lost, the command position for that period is not updated.
In this case, the Unit will receive the same command position as before, which will result in a travel dis-
tance of 0 or in an immediate stop (velocity 0).
Therefore, refreshing synchronized commands is monitored to prevent the machine from stopping
abruptly or to prevent the stepper motor from step loss.
If the command position cannot be obtained at the expected time, the command position is predicted
based on the previous two command positions so that operation continues.
Additional Information
If the number of consecutive missing synchronization commands exceeds the value that is set
for the Number of Synchronization Command Interpolations parameter, an Incorrect Synchroni-
zation Command error occurs.
When the Output Mode Selection parameter is set to velocity-continuous pulse output, interpolation is
performed as follows when a synchronous command is missing:
• Command position: Command position is presumed based on the previous two commands (primary
interpolation)
• Command velocity: The previous command velocity is retained.
If a normal command is received so that the value set for the Number of Synchronization Command
Interpolations parameter is not exceeded and the Unit recovers from the interpolation control state, the
return operation for that command is performed with position-synchronous pulse output.
8-10-8 Interpolation Control for Missing Synchronization Command
Parameter name
Setting
Default
Remarks
Number of Synchroni-
zation Command
Interpolations
0 to 16 (interpolations)
2
• This parameter sets the maximum num-
ber of interpolations for missing synchro-
nization commands.
• Set this parameter to 0 to disable the
function.
• Changes are applied when the power
supply to the NX Unit is turned ON or the
NX Unit is restarted.
Interpolation for Velocity-continuous Pulse Output
Summary of Contents for NX-EC0112
Page 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Page 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Page 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Page 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Page 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Page 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Page 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Page 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Page 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Page 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Page 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...