![Omron NX-EC0112 User Manual Download Page 123](http://html1.mh-extra.com/html/omron/nx-ec0112/nx-ec0112_user-manual_742777123.webp)
5 - 9
5 I/O Refreshing Methods
NX-series Position Interface Units User’s Manual (W524)
5-
2 I/O Refres
hing
Meth
od
s
5
5-
2-3 I/O Refr
eshing
Method Operation
Synchronous Output Refreshing
• The NX Units that operate with synchronous output refreshing in a Slave Terminal update outputs at
a fixed interval based on Sync0. (Refer to figure (a) in the diagram below.)
Refer to the
NX-series EtherCAT Coupler Unit User’s Manual
(Cat. No. W519-E1-05 or later) for
information on the Slave Terminals that operate with the same timing when more than one Slave Ter-
minal is placed on the same EtherCAT network.
• The Communications Coupler Unit updates the values of the output during I/O refreshing. (See fol-
lowing figure (b).)
• The I/O refreshing interval changes according to the processing conditions of the Communications
Coupler Unit and host communications master (see following figure (c)), so the output refresh interval
is constant. (See following figure (d), (e).)
• The ON/OFF response time is required from when outputs are updated until the output status is set
on the external terminals of the NX Units. (See following figure (f).)
Additional Information
Refer to the
NX-series EtherCAT Coupler Unit User’s Manual
(Cat. No. W519) for details on the
operation of I/O refreshing with connections that do not use the built-in EtherCAT port on the
NJ/NX-series CPU Unit.
The Sysmac Studio automatically calculates the offset
between Sync0 and the output refresh timing.
Constant
Constant
(c) The I/O refresh interval
is not constant.
ON/OFF
response
time
Unit A
Unit B
Not constant
(d) The Sync0 interval is constant.
(e) Constant
Constant
Constant
(b) The Communications Coupler Unit updates
the values of the output during I/O refreshing.
Wait time
Wait time
I/O refreshing on
NX bus
Sync0
Sync0
Sync0
Input refreshing
Output refreshing
(a) All Output Units that operate with synchronous output
refreshing update their outputs at the same time.
(f) Output status is finalized.
Summary of Contents for NX-EC0112
Page 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Page 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Page 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Page 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Page 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Page 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Page 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Page 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Page 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Page 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Page 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...