![Omron NX-EC0112 User Manual Download Page 423](http://html1.mh-extra.com/html/omron/nx-ec0112/nx-ec0112_user-manual_742777423.webp)
A - 35
Appendices
NX-series Position Interface Units User’s Manual (W524)
A-
2 Ob
ject
List
s
A
A-
2-2 Increme
nt
al E
n
coder
Input U
nit
s
• This displays the time when the present value data was changed.
• The following table shows the bit configuration of the Encoder Counter Operation Command object.
Index
(hex)
Subin-
dex
(hex)
Object name
Default
Data range
Unit
Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
6010
---
Time Stamp
---
---
---
---
---
---
---
00
Number of Entries
*1
*1. The values for the NX-EC0112, NX-EC0122, NX-EC0132, or NX-EC0142 are 1. The values for the NX-EC0212 or
NX-EC0222 are 2.
*1
---
USINT
RO
No
---
01
CH1 Time Stamp
0
0000000000000000 to
FFFFFFFFFFFFFFFF
hex
---
ULINT
RO
Yes
---
02
CH2 Time Stamp
*2
*2. This object does not exist on the NX-EC0112, NX-EC0122, NX-EC0132, and NX-EC0142.
0
0000000000000000 to
FFFFFFFFFFFFFFFF
hex
---
ULINT
RO
Yes
---
Index
(hex)
Subin-
dex
(hex)
Object name
Default
Data range
Unit
Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
7000
---
Encoder Counter Opera-
tion Command
---
---
---
---
---
---
---
00
Number of Entries
*1
*1. The values for the NX-EC0112, NX-EC0122, NX-EC0132, or NX-EC0142 are 1. The values for the NX-EC0212 or
NX-EC0222 are 2.
*1
---
USINT
RO
No
---
01
Ch1 Encoder Counter
Operation Command
0000 hex
0000 to
FFFF hex
---
WORD
RW
Yes
N
02
Ch2 Encoder Counter
Operation Command
*2
*2. This object does not exist on the NX-EC0112, NX-EC0122, NX-EC0132, and NX-EC0142.
0000 hex
0000 to
FFFF hex
---
WORD
RW
Yes
N
Bit
Data name
Description
0
Counter Enable
1: Enable counter command.
0: Disable counter command.
1
Internal Reset Execution
0 to 1: Reset of present value started.
2
Internal Latch Execution
0 to 1: Internal latch started.
3
Preset Execution
0 to 1: Preset of present value started.
4
External Reset Enable
1: Reset for external reset enabled.
0: Reset for external reset disabled.
5
Phase Z Reset Enable
1: Reset for phase-Z signal enabled.
0: Reset for phase-Z signal disabled.
6
External Reset Completed Flag Clear 0 to 1: Reset Completed Flag cleared for external reset.
7
Phase Z Reset Completed Flag Clear 0 to 1: Reset Completed Flag cleared for phase Z.
Summary of Contents for NX-EC0112
Page 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Page 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Page 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Page 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Page 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Page 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Page 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Page 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Page 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Page 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Page 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...