![Omron NX-EC0112 User Manual Download Page 438](http://html1.mh-extra.com/html/omron/nx-ec0112/nx-ec0112_user-manual_742777438.webp)
Appendices
A - 50
NX-series Position Interface Units User’s Manual (W524)
• Set the start bit position for multi-turn data.
• If the sum of the values set for the Multi-turn Data Start Bit and the Multi-turn Data Length objects is
greater than the Valid Data Length object, SSI communications are disabled and an SSI Data Setting
Error event occurs.
• Set this object to the data length for multi-turn data.
• If the sum of the values set for the Multi-turn Data Length, Single-turn Data Length, and Status Data
Length objects is greater than 32, SSI communications are disabled and an SSI Data Setting Error
event occurs.
• Set this object to the start bit position for status data.
• If the sum of the values set for the Status Data Start Bit and the Status Data Length objects is greater
than the Valid Data Length object, SSI communications are disabled and the SSI Data Setting Error
event occurs.
Index
(hex)
Subin-
dex
(hex)
Object name
Default
Data range
Unit
Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
5008
---
Multi-turn Data Start Bit
---
---
---
---
---
---
---
00
Number of Entries
*1
*1. The values for the NX-ECS112 are 1. The values for the NX-ECS212 are 2.
*1
---
USINT
RO
No
---
01
Ch1 Multi-turn Data Start Bit
0
0 to 31
---
USINT
RW
No
Y
02
Ch2 Multi-turn Data Start Bit
*2
*2. This object does not exist on the NX-ECS112.
0
0 to 31
---
USINT
RW
No
Y
Index
(hex)
Subin-
dex
(hex)
Object name
Default
Data range
Unit
Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
5009
---
Multi-turn Data Length
---
---
---
---
---
---
---
00
Number of Entries
*1
*1. The values for the NX-ECS112 are 1. The values for the NX-ECS212 are 2.
*1
---
USINT
RO
No
---
01
Ch1 Multi-turn Data
Length
12
0 to 32
Bit
USINT
RW
No
Y
02
Ch2 Multi-turn Data
Length
*2
*2. This object does not exist on the NX-ECS112.
12
0 to 32
Bit
USINT
RW
No
Y
Index
(hex)
Subin-
dex
(hex)
Object name
Default
Data range
Unit
Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
500A
---
Status Data Start Bit
---
---
---
---
---
---
---
00
Number of Entries
*1
*1. The values for the NX-ECS112 are 1. The values for the NX-ECS212 are 2.
*1
---
USINT
RO
No
---
01
Ch1 Status Data Start Bit
0
0 to 31
---
USINT
RW
No
Y
02
Ch2 Status Data Start Bit
*2
*2. This object does not exist on the NX-ECS112.
0
0 to 31
---
USINT
RW
No
Y
Summary of Contents for NX-EC0112
Page 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Page 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Page 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Page 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Page 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Page 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Page 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Page 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Page 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Page 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Page 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...