6 Incremental Encoder Input Units
6 - 70
NX-series Position Interface Units User’s Manual (W524)
You can measure the period between the rising edges or falling edges of the input pulse.
For phase-A input pulses, the rate of change of the specified edge is measured and the most recent
measurement result for the latest NX bus I/O refresh is returned.
This measurement is not performed in sync with the NX bus synchronization cycle.
Example Operation for Measuring Both Edges
*1. The pulse period measurement counter retains the most recent value while the function is disabled.
*2. The operation is reset if the Overflow Flag is ON when the function is disabled.
6-9-11 Pulse Period Measurement
Item
Specifications
Remarks
Measurement target
Phase-A input pulse
Measures the pulse frequency according to the
specifications listed in the column to the left, regard-
less of the pulse input method, counting direction, or
multiplier.
Detection method
• Between rising edges
• Between falling edges
• Between both edges
Measurable range
1 to 4,294,967,295 (
×
100 ns)
(100 ns to 429.4967295 s)
The data type is UDINT.
However, frequency measurements that exceed the
maximum response frequency may not be accurate.
If the maximum measurable value is exceeded, the
value returns to zero.
Measurement resolution
(minimum measurement
unit)
100 ns
Times below 100 ns are rounded up.
4,294,967,295
0
aaa
bbb
ccc
Phase-A input pulse
ddd
Output (CPU Unit to Unit)
Input (Unit to CPU Unit)
Pulse Period Measure-
ment Enable bit
Pulse Period Measure-
ment Enabled
Started.
Restarted.
Started.
Time
Pulse Period Measurement Value Clear bit
Pulse Period Measurement Value
Overflow Flag Clear bit
Pulse Period Measured Value
0
aaa
bbb
0
0
Pulse Period Measurement
Value Clear Completed bit
Pulse Period Measurement
Value Overflow Flag
ccc
ddd
Pulse period
measurement
started.
Pulse period
measurement value
overflow occurred.
Pulse Period
Measurement Value
Clear executed.
Pulse period
measurement value
overflow occurred.
Pulse Period
Measurement Value
Overflow Flag Clear
executed.
Pulse period
measurement
stopped.
Pulse period
measurement
started.
(*1)
(*2)
Summary of Contents for NX-EC0112
Page 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Page 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Page 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Page 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Page 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Page 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Page 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Page 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Page 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Page 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Page 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...