![Omron NX-EC0112 User Manual Download Page 422](http://html1.mh-extra.com/html/omron/nx-ec0112/nx-ec0112_user-manual_742777422.webp)
Appendices
A - 34
NX-series Position Interface Units User’s Manual (W524)
• The following table shows the bit configuration of the Pulse Period Measurement Status object.
Index
(hex)
Subin-
dex
(hex)
Object name
Default
Data range
Unit
Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
6008
---
Pulse Period Measure-
ment Status
---
---
---
---
---
---
---
00
Number of Entries
*1
*1. The values for the NX-EC0112, NX-EC0122, NX-EC0132, or NX-EC0142 are 1. The values for the NX-EC0212 or
NX-EC0222 are 2.
*1
---
USINT
RO
No
---
01
Ch1 Pulse Period Mea-
surement Status
00 hex
00 to FF hex
---
BYTE
RO
Yes
---
02
Ch2 Pulse Period Mea-
surement Status
*2
*2. This object does not exist on the NX-EC0112, NX-EC0122, NX-EC0132, and NX-EC0142.
00 hex
00 to FF hex
---
BYTE
RO
Yes
---
Bit
Status name
Description
0
Pulse Period Measurement
Enabled
1: Pulse period measurement enabled.
0: Pulse period measurement disabled.
1
Pulse Period Measurement
Value Clear Completed
1: Pulse period measurement value clear completed.
0: Pulse period measurement value clear bit is 0.
2
Pulse Period Measurement
Value Overflow Flag
1: Pulse period measurement value overflow occurred.
0: Pulse period measurement value overflow did not occur.
Index
(hex)
Subin-
dex
(hex)
Object name
Default
Data range
Unit
Data type Access
I/O
allo-
cat-
ion
Data
attri-
bute
6009
---
Pulse Period Measured
Value
---
---
---
---
---
---
---
00
Number of Entries
*1
*1. The values for the NX-EC0112, NX-EC0122, NX-EC0132, or NX-EC0142 are 1. The values for the NX-EC0212 or
NX-EC0222 are 2.
*1
---
USINT
RO
No
---
01
Ch1 Pulse Period Mea-
sured Value
0
1 to
4,294,967,295
100 ns
UDINT
RO
Yes
---
02
Ch2 Pulse Period Mea-
sured Value
*2
*2. This object does not exist on the NX-EC0112, NX-EC0122, NX-EC0132, and NX-EC0142.
• The setting range is 100 ns to 429.4967295 s.
0
1 to
4,294,967,295
100 ns
UDINT
RO
Yes
---
Summary of Contents for NX-EC0112
Page 13: ...11 Manual Structure NX series Position Interface Units User s Manual W524...
Page 34: ...Revision History 32 NX series Position Interface Units User s Manual W524...
Page 36: ...Sections in this Manual 34 NX series Position Interface Units User s Manual W524...
Page 78: ...3 Part Names and Functions 3 8 NX series Position Interface Units User s Manual W524...
Page 108: ...4 Installation and Wiring 4 30 NX series Position Interface Units User s Manual W524 Unit...
Page 114: ...4 Installation and Wiring 4 36 NX series Position Interface Units User s Manual W524...
Page 126: ...5 I O Refreshing Methods 5 12 NX series Position Interface Units User s Manual W524...
Page 340: ...8 Pulse Output Units 8 76 NX series Position Interface Units User s Manual W524...
Page 462: ...Appendices A 74 NX series Position Interface Units User s Manual W524...
Page 463: ...I 1 I NX series Position Interface Units User s Manual W524 Index...
Page 466: ...I 4 NX series Position Interface Units User s Manual W524 Index...