6
-64
Self-Diagnosis
The Inverter has a built-in function for self-diagnosing the operations of serial communications interface cir-
cuits. This function is called the self-diagnosis function. The self-diagnosis function connects the communica-
tions parts of the send and receive terminals, receives the data sent by the Inverter and checks if
communications are being performed normally.
Perform the self-diagnosis function using the following procedure.
1. Turn ON the power supply to the Inverter and set 67 (communications test mode) in parameter H1-05
(Terminal S7 Function Selection).
2. Turn OFF the power supply to the Inverter.
3. Perform wiring according to the following diagram while the power supply is turned OFF.
4. Turn ON the terminating resistance. (Turn ON pin 1 on DIP switch 1.)
5. Turn ON the power supply to the Inverter again.
Fig 6.41 Details of Communications Terminals
During normal operation, the Digital Operator displays the frequency reference value.
If an error occurs, a CE (RS-422A/485 communications error) alarm will be displayed on the Digital Operator,
the error contact output will be turned ON and the Inverter operation ready signal will be turned OFF.