Parameter Tables
5
-
35
Multi-function Selections: o2
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
o2-01
LOCAL/
REMOTE key
enable/dis-
able
Sets the Digital Operator Local/
Remote Key
0: Disabled
1: Enabled (Switches between
the Digital Operator and the
parameter settings.)
0 or 1
1
No
A
505H
6-80
Local/Remote
Key
o2-02
STOP key
during control
circuit terminal
operation
Sets the Stop Key in the run
mode.
0: Disabled (When the run com-
mand is issued from and exter-
nal terminal, the Stop Key is
disabled.)
1: Enabled (Effective even
during run.)
0 or 1
1
No
A
506H
6-80
Oper STOP
Key
o2-03
Parameter ini-
tial value
Clears or stores user initial val-
ues.
0: Stores/not set
1: Begins storing (Records the
set parameters as user initial
values.)
2: All clear (Clears all recorded
user initial values)
When the set parameters are
recorded as user initial values,
1110 will be set in A1-03.
0 to 2
0
No
A
507H
6-80
User Defaults
o2-04
kVA selection
Do not set unless using a control
board from an Inverter with a dif-
ferent capacity.
0 to FF
0
*
No
A
508H
-
Inverter Model
o2-05
Frequency
reference set-
ting method
selection
When the frequency reference is
set on the Digital Operator fre-
quency reference monitor, sets
whether the Enter Key is neces-
sary.
0: Enter Key needed
1: Enter Key not needed
When set to 1, the Inverter
accepts the frequency reference
without Enter Key operation.
0 or 1
0
No
A
509H
6-80
Operator
M.O.P.
o2-06
Operation
selection
when digital
operator is
disconnected
Sets the operation when the Digi-
tal Operator is disconnected.
0: Disabled (Operation continues
even if the Digital Operator is
disconnected.)
1: Enabled (OPR is detected at
Digital Operator disconnec-
tion. Inverter output is cut off
and fault contact is operated.)
0 or 1
0
No
A
50AH
-
Oper Detec-
tion
o2-07
Cumulative
operation time
setting
Sets the cumulative operation
time in hour units.
Operation time is calculated from
the set values.
0 to
65535
0 hr
No
A
50BH
6-80
Elapsed Time
Set