Parameter Tables
5
-
17
Jump Frequencies: d3
Field Weakening: d6
Parame-
ter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
d3-01
Jump fre-
quency 1
Set the center values of the jump
frequencies in Hz.
This function is disabled by set-
ting the jump frequency to 0 Hz.
Always ensure that the following
applies:
d3-01
≥
d3-02
≥
d3-03
Operation in the jump frequency
range is prohibited but during
acceleration and deceleration, the
speed changes smoothly without
jumping.
0.0 to
120.0
0.0 Hz
No
A
294H
6-24
Jump Freq 1
d3-02
Jump fre-
quency 2
0.0 Hz
No
A
295H
6-24
Jump Freq 2
d3-03
Jump fre-
quency 3
0.0 Hz
No
A
296H
6-24
Jump Freq 3
d3-04
Jump fre-
quency width
Sets the jump frequency band-
width in Hz.
The jump frequency range will be
the jump frequency ± d3-04.
0.0 to
20.0
1.0 Hz
No
A
297H
6-24
Jump
Bandwidth
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
d6-01
Field weaken-
ing level
Set the Inverter output voltage
when the field weakening com-
mand is input.
It is enabled when the field weak-
ening command is set for a multi-
function input.
Set the level as a percentage tak-
ing the voltage set in the V/f pat-
tern as 100%.
0 to
100
80%
No
A
2A0H
6-28
Field-Weak
Lvl
d6-02
Field fre-
quency
Set the lower limit in Hz of the
frequency range where field con-
trol is valid.
The field weakening command is
valid only at frequencies above
this setting and only when the
speed is in agreement with the
current speed reference.
0.0 to
120.0
0.0 Hz
No
A
2A1H
6-28
Field-Weak
Freq