Parameter Tables
5
-
21
Multi-function Digital Outputs: H2
Multi-function Digital Output Functions
1E
Analog frequency reference sample/hold
6-47
20 to
2F
External fault (Desired settings possible)
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
6-49
34
PI soft starter
6-67
61
External search command 1 (ON: Speed search from maximum output frequency)
6-39
62
External search command 2 (ON: Speed search from set frequency)
6-39
63
Field weakening command (ON: Field weakening control set for d6-01 and d6-02)
6-28
64
External speed search command 3
6-39
67
Communications test mode
6-64
68
High-slip braking (HSB)
6-14
69
Jog Frequency 2
–
6A
Drive enable
–
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
H2-01
Terminal M1-
M2 function
selection
Multi-function contact output 1
0 to 38
0
No
A
40BH
-
Term M1-M2
Sel
H2-02
Terminal M3-
M4 function
selection
Multi-function contact output 2
0 to 38
1
No
A
40CH
-
Term M3-M4
Sel
Setting
Value
Function
Page
0
During run (ON: run command is ON or voltage is being output)
-
1
Zero-speed
6-26
2
Frequency agree 1 (L4-02 used.)
-
3
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and during frequency
agree)
-
4
Frequency (F-OUT) detection 1 (ON: +L4-01
≥
output frequency
≥
-L4-01, L4-02 used)
-
5
Frequency (F-OUT) detection 2 (ON: Output frequency
≥
+L4-01 or output frequency
≤
-L4-01,
L4-02 used)
-
6
Inverter operation ready
READY: After initialization, no faults
-
7
During DC bus undervoltage (UV) detection
-
8
During baseblock (ON: during baseblock)
-
9
Frequency reference selection (ON: Frequency reference from Operator)
-
A
Run command selection status (ON: Run command from Operator)
-
B
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detection at ON)
6-31
C
Loss of frequency reference (Effective when 1 is set for L4-05)
6-43
Set-
ting
Value
Function
Page