6
-84
Writing parameter Set Values Stored in the Digital Operator to the Inverter (COPY)
To write parameter set values stored in the Digital Operator to the Inverter, make the settings using the follow-
ing method.
If an error is displayed, set the parameters again. Error displays and their descriptions are shown below. (Refer
to Chapter 7 Errors when Using Digital Operator Copy Function.)
Table 6.3 COPY Function Procedure
Step
No.
Digital Operator Display
Explanation
1
Press the MENU key and select advanced pro-
gramming mode.
2
Press the ENTER key and select the parameters
monitor display.
3
Display o3-01 (Copy Function Selection) using
the Increment key and Decrement key.
4
Press the ENTER key and select the parameters
setting display.
5
Change the set value to 2 using the Increment
Key.
6
Set the changed data using the ENTER key. The
COPY function will start.
7
If the COPY function ends normally, End is dis-
played on the Digital Operator. Parameter o3-
01 is automatically reset to 0 and then the dis-
play returns to o3-01.
Error Display
Description
Inverter product code and Inverter software number are different.
Inverter capacity with which you are trying to copy and the Inverter capacity stored in the Digital
Operator are different.
The Inverter control method in which you are trying to copy and the Inverter control method stored in
the Digital Operator are different.
Comparison between the parameter written to the Inverter and the parameter in the Digital Operator
are different.
After copying has ended, the checksum between the sum value of the Inverter parameter and the sum
value of the Digital Operator parameter are different.