Parameters Setable in Quick Programming Mode
The minimum parameters required for Inverter operation can be monitored and set in quick programming
mode. The parameters displayed in quick programming mode are listed in the following table. These and all
other parameters, are also displayed in advanced programming mode.
Refer to the overview of modes on page 3-5 for an overview of quick programming mode.
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485 Reg-
ister
LCD Display
b1-01
Reference
selection
Set the frequency reference input
method.
0: Digital Operator
1: Control circuit terminal (analog
input)
2: RS-422A/485 communications
3: Option Card
0 to 3
1
No
Q
180H
Reference
Source
b1-02
Operation
method selec-
tion
Set the run command input method
0: Digital Operator
1: Control circuit terminal (sequence
input)
2: RS-422A/485 communications
3: Option Card
0 to 3
1
No
Q
181H
Run Source
b1-03
Stopping
method selec-
tion
Select stopping method when stop
command is input.
0: Ramp to stop
1: Coast to stop
2: DC braking stop (Stops faster than
coast to stop, without regenerative
operation.)
3: Coast to stop with timer (Run com-
mands are disregarded during
deceleration time.)
0 to 3
0
No
Q
182H
Stopping
Method
C1-01
Acceleration
time 1
Set the acceleration time in seconds
for the output frequency to climb from
0% to 100%.
0.0 to 6000.0
10.0 s
Yes
Q
200H
Accel Time 1
C1-02
Deceleration
time 1
Set the deceleration time in seconds
for the output frequency to fall from
100% to 0%.
Yes
Q
201H
Decel Time 1
C6-02
Carrier fre-
quency selec-
tion
Select carrier wave fixed pattern.
Select F to enable detailed settings
using parameters C6-03 to C6-07.
1 to F
6
No
Q
224H
Carrier-
FreqSel