9
-2
Standard Inverter Specifications
Specifications by Model
Specifications are given by model in the following tables.
200V Class
* 1. The maximum applicable motor output is given for a standard 4-pole OMRON motor. When selecting the actual motor and Inverter, be sure that the Inverter's
rated current is applicable for the motor's rated current.
* 2. A 3-wire transformer is required on the power supply for 12-phase rectification.
Table 9.1 200 V Class Inverters
Model Number 3G3PV-
A2004
A2007
A2015
A2022
A2037
A2055
A2075
A2110
A2150
A2185
A2220
A2300
A2370
A2450
A2550
A2750
A2900
Max. applicable motor output
(kW)
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
Rated output capacity
(kVA)
1.2
1.6
2.7
3.7
5.7
8.8
12
17
22
27
32
44
55
69
82
110
130
Rated output current (A)
3.2
4.1
7.0
9.6
15
23
31
45
58
71
85
115
145
180
215
283
346
Max. output voltage (V)
3-phase; 200, 208, 220, 230 or 240 VAC
(Proportional to input voltage.)
Max. output frequency
(Hz)
120 Hz max.
Rated voltage (V)
Rated frequency (Hz)
3-phase, 200/208/220/230/240 VAC, 50/60 Hz
Allowable voltage fluctua-
tion
+ 10%, - 15%
Allowable frequency fluc-
tuation
±5%
Measures
for power
supply
harmonics
DC reactor
Optional
Built in
12-phase rec-
tification
Not possible
Possible
*2
Model Number 3G3PV-
B2220
B2300
B2370
B2450
B2550
B2750
B2900
B211K
Max. applicable motor output
(kW)
22
30
37
45
55
75
90
110
Rated output capacity
(kVA)
32
44
55
69
82
110
130
160
Rated output current (A)
85
115
145
180
215
283
346
415
Max. output voltage (V)
3-phase 200, 208, 220, 230 or 240 VAC
(Proportional to input voltage)
Max. output frequency
(Hz)
120 Hz max.
Rated voltage (V)
Rated frequency (Hz)
3-phase, 200/208/220/230/240 VAC, 50/60 Hz
Allowable voltage fluctua-
tion
+ 10%, - 15%
Allowable frequency fluc-
tuation
±5%
Measures
for power
supply
harmonics
DC reactor
Built in
12-phase rec-
tification
Possible
*2
Out
put
r
a
ti
ngs
P
o
w
er s
upp
ly
ch
ar
ac
te
ri
st
ic
s
Con
tr
o
l c
h
ar
ac
te
ri
st
ic
s
Out
put
r
a
ti
n
g
s
Po
wer
su
ppl
y
cha
ra
c
te
ri
st
ic
s
Cont
ro
l ch
ar
ac
te
ri
st
ic
s