Parameter Tables
5
-
7
Parameter Tables
A: Setup Settings
Initialize Mode: A1
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD Display
A1-00
Language
selection for
Digital Opera-
tor display
Used to select the language
displayed on the Digital
Operator Display.
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portugese
This parameter is not initial-
ized by the initialize opera-
tion.
0 to 6
0
Yes
A
100H
–
Select Lan-
guage
A1-01
Parameter
access level
Used to set the parameter
access level (set/read.)
0: Monitoring only (Moni-
toring drive mode and
setting A1-01 and A1-
04.)
2: Advanced
(Parameters can be read
and set in both, quick
programming mode (Q)
and advanced pro-
gramming (A) mode.)
0 or 2
2
Yes
A
101H
6-6
6-31
Acces Level
A1-03
Initialize
Used to initialize the param-
eters using the specified
method.
0:
No initializing
1110: Initializes using the
Parameters
2220: Initializes using a
two-wire sequence.
(Initializes to the
factory setting.)
3330: Initializes using a
three-wire sequence.
0 to
3330
0
No
A
103H
–
Init
Parameters
A1-04
Password
Password input when a pass-
word has been set in A1-05.
This function write-protects
some parameters of the ini-
tialize mode.
If the password is changed,
A1-01 to A1-03 parameters
can no longer be changed.
(Programming mode param-
eters can be changed.)
0 to
9999
0
No
A
104H
6-86
Enter Pass-
word