Parameter Tables
5
-
45
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V class
Inverters with outputs of 0.4 to 11 kW.
* If C6-02 is set to 0, 1 or F and the initial value of C6-03 and C6-04 is 2.0 kHz, the initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4: 10
kHz, 5: 12.5 kHz and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 7.5 kW or more, the Inverter
rated current will need to be reduced.
Param-
eter
Number
Name
Unit
Factory Setting
-
Inverter Capacity
kW
18.5
22
30
37
45
55
75
90
110
o2-04
kVA selection
-
9
A
B
C
D
E
F
10
11
b8-04
Energy-saving coeffi-
cient
-
57.87
51.79
46.27
38.16
35.78
31.35
23.10
23.10
23.10
C4-02
Torque compensation
primary delay time
ms
200
200
1000
1000
1000
1000
1000
1000
1000
C6-02
Carrier frequency selec-
tion*
-
6
6
4
3
3
3
3
3
1
E2-01
Motor rated current
A
65.8
77.2
105.0
131.0
160.0
190.0
260.0
260.0
260.0
E2-05
Motor line-to-line resis-
tance
Ω
0.101
0.079
0.064
0.039
0.030
0.022
0.023
0.023
0.023
L2-02
Momentary power loss
ridethru time
s
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-03
Min. baseblock (BB)
time
s
1.0
1.0
1.1
1.1
1.2
1.2
1.3
1.5
1.7
L2-04
Voltage recovery time
s
0.6
0.6
0.6
0.6
0.6
1.0
1.0
1.0
1.0
L8-02
Overheat pre-alarm level
°
C
95
95
95
95
95
95
95
95
95