Parameter Tables
5
-
47
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V class
Inverters with outputs of 0.4 to 11 kW.
* If C6-02 is set to 0, 1 or F and the initial value of C6-03 and C6-04 is 2.0 kHz, the initial settings for C6-02 are as follows: 2: 5.0 kHz, 3: 8.0 kHz, 4:
10 kHz, , 5: 12.5 kHz and 6: 15 kHz. If the carrier frequency is set higher than the factory setting for Inverters with outputs of 7.5 kW or more, the Inverter
rated current will need to be reduced.
Param-
eter-
Number
Name
Unit
Fac-
tory
Set-
ting
-
Inverter Capacity
kW
160
o2-04
kVA selection
-
34
b8-04
Energy-saving coeffi-
cient
-
30.13
C4-02
Torque compensation
primary delay time
ms
1000
C6-02
Carrier frequency selec-
tion
*
-
2
E2-01
Motor rated current
A
270.0
E2-05
Motor line-to-line resis-
tance
Ω
0.029
L2-02
Momentary power loss
ridethru time
s
2.0
L2-03
Min. baseblock (BB)
time
s
1.8
L2-04
Voltage recovery time
s
1.0
L8-02
Overheat pre-alarm level
°
C
100