Standard Inverter Specifications
9
-
3
400 V Class
Table 9.2 400 V Class Inverters
Model Number 3G3PV-
A4004
A4007
A4015
A4022
A4037
A4040
A4055
A4075
A4110
A4150
A4185
Max. applicable motor output
(kW)
0.4
0.75
1.5
2.2
3.7
4.0
5.5
7.5
11
15
18.5
Rated output capacity
(kVA)
1.4
1.6
2.8
4.0
5.8
6.6
9.5
13
18
24
30
Rated output current (A)
1.8
2.1
3.7
5.3
7.6
8.7
12.5
17
24
31
39
Max. output voltage (V)
3-phase; 380, 400, 415, 440, 460 or 480 VAC (Proportional to input voltage.)
Max. output frequency
(Hz)
120 Hz max.
Rated voltage (V)
Rated frequency (Hz)
3-phase, 380, 400, 415, 440, 460 or 480 VAC, 50/60 Hz
Allowable voltage fluctua-
tion
+ 10%, - 15%
Allowable frequency fluc-
tuation
±5%
Measures
for power
supply
harmonics
DC reactor
Optional
12-phase rec-
tification
Not possible
Model Number 3G3PV-
A4220
A4300
A4370
A4450
A4550
A4750
A4900
A411K
A413K
A416K
Max. applicable motor output
(kW)
22
30
37
45
55
75
90
110
132
160
Rated output capacity
(kVA)
34
46
57
69
85
110
140
160
200
230
Rated output current (A)
45
60
75
91
112
150
180
216
260
304
Max. output voltage (V)
3-phase, 380, 400, 415, 440, 460 or 480 VAC (Proportional to input voltage.)
Max. output frequency
(Hz)
120 Hz max.
Max. voltage (V)
Rated frequency (Hz)
3-phase, 380, 400, 415, 440, 460 or 480 VAC, 50/60 Hz
Allowable voltage fluctua-
tion
+ 10%, - 15%
Allowable frequency fluc-
tuation
±5%
Measures
for power
supply
harmonics
DC reactor
Built in
12-phase rec-
tification
Possible
*2
O
u
tp
ut
ra
tin
g
s
P
o
w
er
s
upp
ly
ch
ar
act
er
ist
ic
s
C
o
nt
ro
l ch
a
ra
cte
ri
st
ic
s
O
u
tp
ut
ra
tin
g
s
Po
w
e
r su
p
p
ly
c
h
ar
ac
te
ris
ti
cs
C
o
n
tr
o
l
c
h
ar
ac
te
ri
sti
cs