6
-80
Digital Operator Functions
Setting Digital Operator Functions
Related Parameters
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD Display
o1-02
Monitor selection after
power up
Set the monitor item to be displayed when the power sup-
ply is turned ON.
1: Frequency reference
2: Output frequency
3: Output current
4: The monitor item set for o1-01
1 to 4
1
Yes
A
Power-ON Monitor
o1-03
Frequency units of refer-
ence setting and monitor
Sets the units that will be set and displayed for the fre-
quency reference and frequency monitor.
0: 0.01
Hz
units
1:
0.01% (Maximum output frequency is
100%)
2 to 39:
rotation per minute (rpm) (Sets the motor
poles)
40 to 39999: User desired display
Set the desired values for setting and dis-
play for the max. output frequency.
Example: When the max. output frequency value is 200.0,
set 12000.
0 to
39999
0
No
A
Display Scaling
o2-01
LOCAL/REMOTE key
enable/disable
Set the run method selection key (LOCAL/REMOTE Key)
function.
0: Disabled
1: Enabled (Switches between the Digital Operator and
the parameter settings.)
0 or 1
1
No
A
Local/Remote Key
o2-02
STOP Key during con-
trol circuit terminal oper-
ation
Set the STOP Key in the run mode.
0: Disabled (When the run command is issued from an
external terminal, the Stop Key is disabled.)
1: Enabled (Effective even during run.)
0 or 1
1
No
A
Oper STOP Key
o2-03
User parameter initial
value
Clears or stores user initial values.
0: Stores/not set
1: Begins storing (Records the set parameters as user
initial values.)
2: All clear (Clears all recorded user initial values)
When the set parameters are recorded as user initial val-
ues, 1110 will be set in A1-03.
0 to 2
0
No
A
User Defaults
o2-05
Frequency reference
setting method selection
When the frequency reference is set on the Digital Opera-
tor frequency reference monitor, sets whether the Enter
Key is necessary.
0: Enter Key needed
1: Enter Key not needed
When set to 1, the Inverter accepts the frequency reference
without Enter Key operation.
0 or 1
0
No
A
Operator M.O.P.
o2-07
Cumulative operation
time setting
Sets the cumulative operation time in hour units.
Operation time is calculated from the set values.
0 to
65535
0
No
A
Elapsed Time Set
o2-10
Fan operation time set-
ting
Set the initial value of the fan operation time using hour
units.
The operation time accumulates from the set value.
0 to
65535
0
No
A
Fan ON Time Set
Set digit number
excluding the decimal
point.
Set the number of
digits below the
decimal point to
display.