Terminal Function Parameters: H
The following settings are made with the terminal function parameters (H parameters): Settings for external
terminal functions.
Multi-function Digital Inputs: H1
* The values in parentheses indicate initial values when initialized in 3-wire sequence.
Multi-function Digital Input Functions
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD
Display
H1-01
Terminal S3
function selec-
tion
Multi-function contact input 1
0 to 77
24
No
A
400H
-
Terminal S3
Sel
H1-02
Terminal S4
function selec-
tion
Multi-function contact input 2
0 to 77
14
No
A
401H
-
Terminal S4
Sel
H1-03
Terminal S5
function selec-
tion
Multi-function contact input 3
0 to 77
3 (0)
*
No
A
402H
-
Terminal S5
Sel
H1-04
Terminal S6
function selec-
tion
Multi-function contact input 4
0 to 77
4 (3)
*
No
A
403H
-
Terminal S6
Sel
H1-05
Terminal S7
function selec-
tion
Multi-function contact input 5
0 to 77
6 (4)
*
No
A
404H
-
Terminal S7
Sel
Set-
ting
Value
Function
Page
0
3-wire sequence (Forward/Reverse Run command)
6-9
1
Local/Remote selection (ON: Operator, OFF: parameter setting)
6-46
2
Option/Inverter selection (ON: Option Card)
6-48
3
Multi-step speed reference 1
When H3-05 is set to 0, this function is combined with the master/auxiliary speed switch.
6-6
4
Multi-step speed reference 2
6-6
6
Jog frequency command (higher priority than multi-step speed reference)
6-6
7
Accel/decel time 1
-
8
External baseblock NO (NO contact: Baseblock at ON)
6-46
9
External baseblock NC (NC contact: Baseblock at OFF)
6-46
F
Not used (Set when a terminal is not used)
-
12
FJOG command (ON: Forward run at jog frequency d1-17)
6-48
14
Fault reset (Reset when turned ON)
7-2
19
PI control disable (ON: PI control disabled)
6-67
1B
Parameters write enable (ON: All parameters can be written-in. OFF: All parameters other than
frequency monitor are write protected.)
6-86