![background image](http://html1.mh-extra.com/html/omron/i537-e2-01/i537-e2-01_user-manual_743212161.webp)
Improved Operating Efficiency
6
-
29
Hunting-prevention Function
The hunting-prevention function suppresses hunting when the motor is operating with a light load.
Related Parameters
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
LCD
Display
N1-01
Hunting-prevention
function selection
0: Hunting-prevention function disabled
1: Hunting-prevention function enabled
The hunting-prevention function suppresses hunting when
the motor is operating with a light load.
If high response is to be given priority over vibration sup-
pression, disable the hunting-prevention function.
0 or 1
1
No
A
Hunt Prev Select
N1-02
Hunting-prevention gain
Set the hunting-prevention gain multiplication factor.
Normally, there is no need to make this setting.
Make the adjustments as follows:
• If vibration occurs with light load, increase the setting.
• If the motor stalls, reduce the setting.
If the setting is too large, the voltage will be too sup-
pressed and the motor may stall.
0.00 to
2.50
1.00
No
A
Hunt Prev Gain