Parameter Tables
5
-
31
* The factory setting depends upon the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
L8-03
Operation
selection after
overheat pre-
alarm
Sets the operation for when the
Inverter overheat pre-alarm
occurs.
0: Decelerate to stop in decelera-
tion time C1-02.
1: Coast to stop
2: Fast stop in fast-stop time C1-
09.
3: Continue operation (Monitor
display only.)
A fault will be given in setting 0
to 2 and a minor fault will be
given in setting 3.
0 to 3
3
No
A
4AFH
6-45
OH Pre alarm
Sel
L8-09
Ground pro-
tection selec-
tion
0:Disabled
1:Enabled
0 or 1
1
No
A
4B5H
-
Ground Fault
Sel
L8-11
Cooling fan
control delay
time
Set the time in seconds to delay
turning OFF the cooling fan after
the cooling fan OFF command is
received.
0 to
300
60 s
No
A
4B7H
-
Fan Delay
Time
L8-12
Ambient tem-
perature
Set the ambient temperature.
45 to
60
45
°
C*
No
A
4B8H
-
Ambient Temp
L8-15
OL2 charac-
teristics selec-
tion at low
speeds
0: OL2 characteristics at low
speeds disabled.
1: OL2 characteristics at low
speeds enabled.
0 or 1
1
No
A
4BBH
-
OL2 Sel @ L-
Spd
L8-18
Soft CLA
selection
0: Disabled (gain = 0)
1: Enabled
0 or 1
1
No
A
4BFH
-
Soft CLA Sel
Param-
eter-
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485
Register
Page
LCD