5
-6
* 1. The factory setting depends on the Inverter capacity.
* 2. These are values for a 200 V class Inverter. Values for a 400 V class Inverter are double.
* 3. After autotuning, E1-13 will contain the same value as E1-05.
* 4. The factory setting depends on the Inverter capacity. (The value for a 200 V Class Inverter for 0.4 kW is given.)
* 5. The setting range is from 10% to 200% of the Inverter rated output current. (The value for a 200 V Class Inverter for 0.4 kW is given.)
E2-01
Motor rated
current
Set the motor rated current in Amps.
This set value becomes the base value
for motor protection, torque limit and
torque control. It is an input data for
autotuning.
0.32 to
6.40
*5
1.90 A
*4
No
Q
30EH
Motor Rated
FLA
H4-02
Gain (termi-
nal FM)
Set the voltage level gain for multi-
function analog output 1.
Set the number of multiples of 10 V to
be output as the 100% output for the
monitor items. Voltage output from
the terminals, however, have a 10 V
max. meter calibration function.
0.0 to
1000.0
100%
Yes
Q
41EH
Terminal FM
Gain
H4-05
Gain (termi-
nal AM)
Set the voltage level gain for multi-
function analog output 2.
0.0 to
1000.0
50%
Yes
Q
421H
Terminal AM
Gain
L1-01
Motor protec-
tion selection
Set to enable or disable the motor
overload protection function using the
electronic thermal relay.
0: Disabled
1: General-purpose motor protection
In some applications when the Inver-
ter power supply is turned off, the
thermal value is reset, so even if this
parameter is set to 1, protection may
not be effective.
When several motors are connected to
one Inverter, set to 0 and ensure that
each motor is equipped with a protec-
tion device.
0 or 1
1
No
Q
480H
MOL Fault
Select
L3-04
Stall preven-
tion selection
during decel-
eration
0: Disabled (Deceleration as set. If
deceleration time is too short, a
main circuit overvoltage may
result.)
1: Enabled (Deceleration is stopped
when the main circuit voltage
exceeds the overvoltage level.
Deceleration restarts when voltage
is returned.)
2: Intelligent deceleration mode
(Deceleration rate is automatically
adjusted so that in Inverter can
decelerate in the shortest possible
time. Set deceleration time is disre-
garded.)
When a braking option (Braking
Resistor, Braking Resistor Unit, Brak-
ing Unit) is used, always set to 0 to 2.
0 to 2
1
No
Q
492H
StallP Decel
Sel
Param-
eter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Access
Level
RS-422A/
485 Reg-
ister
LCD Display