7. EQ100 Settings
7-56
Configuring RS-485 Communications Port
7.6.5.
■
Function
To connect an RS-485-connected measurement device, configure an RS-485 communications
port.
Separately specify the communications conditions for four serial communications ports
(RS-485_1, RS-485_2, RS-485_3, and RS-485_4).
Shown below are factory shipment settings of the communications ports:
Item
Factory Shipment Settings
Communication Speed (bps) 9600
Data Length
7 bits
Parity
Even
Stop Bits
2 bits
RS-485 Protocol
CompoWay/F
■
Setup Steps
1) In the setting menu, click [RS-485 Communications Port Setting].
2) Click the [Set] button of the RS-485 communications port you want to configure
RS-485 Communication Port