12. Appendix
12-5
Overview of Error Status Types and Actions
12.1.1.
Error Status
Types
Definition
Details
Output
Action
Device
Alarm
Status
Indicator
Event
Log
Notificati
on
Communicat
ions Error
(Collecting
status Kept)
A
communications
error occurred
under the
collecting status.
The collecting
status is kept.
Email transmission
error, NTP server
connection failure,
EQ server
connection failure
Temporary
On
Yes
Yes
Check that the
communication
s settings and
the server.
Device Error
(Collecting
status Kept)
A failure of an
EQ100 peripheral
device.
The collecting
status is kept.
Battery not attached
or low battery, LAN
connection error,
sub-LAN connection
error, input pulse
failure, abnormal
internal
temperature, SD
card error (including
SD card not
attached)
Flashing
Yes
Yes (No
for LAN
connecti
on error)
Check the
battery
connection,
LAN cable
connection,
ambient
temperature,
SD card
insertion and
capacity.
Monitoring
Process
Error
(Collecting
status Kept)
A status under
which normal
monitoring
process is not
available due to a
failure in the
collecting status.
The collecting
status is kept.
Data collecting rate
lowered, collected
data lost, data
transfer error, time
synchronization
error, SD write
failure continued,
email transmission
error continued,
monitoring failure
occurred
Long
flashing
Yes
Yes
Check the
target device
status, SD card,
and
communication
s settings.
Setup/status
failure
(transition to
setup
status)
EQ100 cannot
start or continue
the collecting
status.
The status
transitions to the
setup status.
Abnormal setup
data, internal
parameter error,
clock failure
Flashing
Yes
No
Please contact
OMRON.
Instrument
Failure
A fatal error:
EQ100 cannot be
started or its
operation cannot
be continued.
CPU runaway
detected, abnormal
program data,
device error,
instrument failure
occurred
On
Yes
Yes
Please contact
OMRON.