2. Specifications
2-10
DIP Switch
2.1.6.
No. Item
Setting
Priority
Remarks
1 (Not used)
Set to Always OFF.
-
-
2 (Not used)
3 (Not used)
4 (Not used)
5 (Not used)
6 (Not used)
7 Write an EQ
project
ON(*) After the startup of EQ100, an
EQ project is automatically
written.
3
Set before turning
on the power or
resetting.
OFF Under normal mode, an EQ
project can be written through
LAN.
8 Update firmware ON(*) After the startup of EQ100,
the firmware is automatically
updated.
2
Set before turning
on the power or
resetting.
OFF Under normal mode, the
firmware can be updated
through LAN.
9 Limit RUN/STOP
button
ON
The RUN/STOP button is
disabled.
This can prevent an
accidental operation of the
RUN/STOP button.
-
Can be set any
time.
OFF The RUN/STOP button is
enabled.
10 Startup Mode
ON(*) EQ100 is started under safe
mode.
1
Set before turning
on the power or
resetting.
OFF EQ100 is started under
normal mode.
* Always set to ON only one of the setup DIP switches SW7, SW8, and SW10. Do not set two
or more switches ON.
* When either of the setup DIP switches SW7, SW8, or SW10 is ON, EQ100 cannot collect
data. To collect data, set all of SW7, SW8, and SW10 to OFF, then reset or restart the
device.
Reference
- For configuration of the setup DIP switches, see "3. Operation Mode and Status".