12. Appendix
12-2
Item
Action
Refer to
A graph view on
the Web UI screen
shows a large
value.
Integrated data value may get large if collecting
has been stopped for a long period of time due to
power off or setup change.
The integrated data can be initialized by clearing
the previous value of integrated data. Note that
clearing the previous value deletes the total value
during the stopped period.
The device alarm
indicator flashes,
turns on, or turns
temporarily on
Check the error details on the "event log
reference" screen.
The device alarm
indicator keeps
flashing due to
improper operation
of SD card
ejection.
Writing to an SD card successfully can recover the
SD card error.
Attach an SD card to write, or stop the collecting
process to clear the failure.
Note that the output of collected data to an SD
card does not erase the collected data in the
internal memory. You can erase the collected data
outputted on the SD card without any problem.
Failed to update
EQ100 settings via
an SD card
Updating of EQ100 settings via an SD card may
fail in the following cases:
- More than one EQ project file exists in the SD
card
- The EQ project file name contains " "(a space
character)
- No EQ project file exists under the "EQ_project"
folder of the SD card, right under the root
- The folder name right under the root does not
comply with case sensitivity, as in "eq_project"
or "EQ_PROJECT" instead of "EQ_project"
- Content of the EQ project file in the SD card is
illegal
- The SD card is not properly attached
This manual: "7.9.2.
Writing EQ Project
File through SD Card"
EQ-Viewer User's
Manual: "4.7. EQ100
Operation and
Management"
Failed to write an
EQ project or
update the
firmware through
an SD card, and
normal ejection
operation of the
SD card cannot be
done
When an error occurred due to an operation using
an SD card, normal SD card ejection operation
using the Save SD Card button may not be
available occasionally.
In such a case, set all the setting DIP switches to
OFRF and press the reset button (or turn off the
power and on again) to restart the EQ100.
After the restart, perform standard SD card
ejection operation to eject the SD card.
Collected data
cannot be
outputted to an SD
card
Use a computer to check that the SD card has
been properly formatted.
Computer's Operation
Manual
Use a computer to check the SD card format,
which must be FAT16 for SD or FAT32 for SDHC.
Computer's Operation
Manual
Check that EQ100 should be configured as
"collecting status".
Time
synchronization
by the SNTP
server cannot be
done
Check the LAN cable connection.
Check that the SNTP server name, LAN settings
(IP address, subnet mask, DNS server, and
default gateway) should be properly configured.