2. Specifications
2-17
Item
Details
SNTP Server
Internal Event Function
A normal event occurrence other than monitoring alarm
and device alarm is collected into the internal memory.
Log to Internal
Memory
An occurred event is saved into the internal memory. The
event log can be checked on the Web UI screen and
outputted as an event log file.
File Output
An event is outputted as an event log file.
Network
Connection
Connection Function LAN connection port: Upper level system (EQ server,
EQ-Manager, SMTP server, SNTP server, FTP server,
FTP client), a computer (Web browser), measurement
device
Sub-LAN connection port: Measurement device, computer
(Web browser)
Web UI Function
A user can view a status, operate the EQ100, view simple
graph, and perform maintenance through a Web browser
on a computer connected to the LAN or sub-LAN
connection port.
Taking Out
Internal Data
File
The following four operations are available:
(1) Collecting by EQ
Server
The EQ server collects data and event logs saved in the
EQ100 internal memory via network.
(2) Operation on
Web UI Screen
Collected data or event log saved in the EQ100 internal
memory is downloaded by operation on the Web UI
screen.
(3) SD Card Output Any of the following operations outputs collected data and
log files saved in the EQ100 internal memory to an SD
card.
- Pressing SD card save button on the EQ100 front end
- Web UI operation: SD card data output operation
If the SD card output setting is configured as "Yes",
collected data saved in the EQ100 internal memory is
saved on an SD card once a day.
(4) FTP transfer
FTP server and FTP client functions are available.
- FTP server function: Acquires collected data files saved
in the EQ100 internal memory via an FTP client and
collected data on an SD card attached to EQ100 or an
event log.
- FTP client function: Sends collected data files saved in
the EQ100 internal memory to the FTP server from
EQ100.
Monitoring
Alarm
Function
Alarm when collected data exceeds upper or lower limit.
Output to a general-purpose output terminal is available
as well.
Email Notification
Function: Monitoring Alarm Email
Log to Internal
Memory
An occurred monitoring alarm is saved into the internal
memory. The event log can be checked on the Web UI
screen and outputted as an event log file.
Status Indication
Device alarm indicator is turned on
Device Alarm
Detection
Function
Detects an instrument failure of EQ100, setup/status,
device, communications, and/or monitoring process.
Email Notification
Function: Device alarm email
Status Indication
Turns on, flashes, long-flashes, or turns temporarily on the
device alarm indicator
Log to Internal
Memory
An occurred device alarm is saved into the internal
memory. An event can be outputted as an event log file.