7. EQ100 Settings
7-60
7.7. Output Setting of Collected Data/Event Log File
Overview
7.7.1.
You can take out collected data files and event log files from EQ100.
Depending on the EQ-Manager setting types, available files differ as shown below:
Yes: Available, N/A: Not available
File Name
EQ-Manager setting
SD Card Output
Setting
FTP Server Setting
FTP Client Setting
Internal System File
Yes
Yes
Yes
User-Specified File
N/A
Yes
Yes
Event Log File
Yes
Yes (*)
N/A
Refer to:
See "7.7.3. SD Card
See "7.7.4. FTP
See "7.7.5. FTP
* Only the event log files saved on an SD card
Shown below are settings to take out the files logged in the EQ100 internal memory.
For operations of Web UI to take out, see "9. Web UI Function".
Precautions for
Correct Use
- EQ100 saves collected data in the internal memory for up to one week. Collected data over
one week are overwritten by newly collected data and collected data files from the oldest
ones.
- Data from measurement devices collected in EQ100 must be saved in a computer or an SD
card attached to EQ100 within one week interval.
- In transferring the collected data to FTP using the FTP client setting, it is necessary to select
the file either from the Internal System file or the User-Specified file.
User-Specified File
7.7.2.
A user can specify and create a file available for FTP.
CSV files are created in a user-specified interval, in UTF-8 coding fixed.
Specify a date format and header column titles for the CSV files.
Files of measured data are created in a specified output interval if the output is specified.
If an interval of one hour is specified for 1-minute collecting, for example, a file of data from
12:00 to 12:59 is created in 12:59.