PART 3: CX-Server Runtime
CHAPTER 3 – Communications
OMRON
CX-Server Runtime_Page 28
Revision 2.0
SYSMAC LINK
SYSMAC LINK is a high speed (2 Mbits/sec) industrial network supporting the connection of multiple C-series,
CV-series, CS series and CJ series PLCs and one or more computers (so enabling the interchange of information
between these devices).
Communications are achieved by either Co-axial or Fibre Optic cabling and employing a SYSMAC LINK
Network Service Board (NSB), and Microsoft Windows device drivers.
Use the following procedure to configure SYSMAC LINK.
1, 2, 3…
1. Ensure the Network Type is SYSMAC LINK.
2. Click on the associated
Settings
pushbutton in the Change PLC dialog.
3. In
the
Network
tab, define the
FINS Destination Address
by entering the
Network
and
Node
.
4. Set
the
Response Timeout(s)
to adjust for a slow network as necessary.
5. Enter the Frame Length in the
Frame Length
field. Refer to
SYSMAC LINK
documentation
for further information.
6. In
the
Driver
field, select the appropriate options from the
Shared RAM
address
and
Interrupt level
fields. Refer to
SYSMAC LINK documentation
for further information.
7. Select
the
OK
pushbutton to save the settings or select the
Cancel
pushbutton to abort the
operation.
SYSMAC NET
SYSMAC NET is a high speed (2 Mbits/sec) LAN employed within medium/large scale systems (C-series PLCs
and CV-series PLCs only).
Connections between the various PLCs and computers is achieved by fibre optics in a ring or loop configuration
allowing the exchange of data between the attached devices. The link is achieved by an NSB and employment of
Microsoft Windows device drivers. Refer to the SYSMAC NET Network Support Board manual for details on
installation.
Use the following procedure to configure SYSMAC NET.
1, 2, 3…
1. Ensure the Network Type is SYSMAC NET.
2. Click on the associated
Settings
pushbutton in the Change PLC dialog.
3. In
the
Network
tab, define the
FINS Destination Address
by entering the
Network
and
Node
.
4. Set
the
Response Timeout(s)
to adjust for a slow network as necessary.
5. Enter the Frame Length in the
Frame Length
field. Refer to
SYSMAC NET
documentation
for further information.
6. Select
the
OK
pushbutton to save the settings or select the
Cancel
pushbutton to abort
the operation.
Controller Link
The Controller Link is an Factory Automation network that can send and receive large data packets flexibly and
easily among the PLCs and IBM PC/AT or compatible computers.
The Controller Link supports data links that enable data sharing and a message service that enables sending and
receiving data when required. Data link areas can be freely set to create a flexible data link system and
effectively use data areas using the CX-Net Network Configuration tool. Refer the to
PLC Tools User Manual
Chapter 8 - CX-Net Network Configuration Tool
for further details.
The network is connected using shielded twisted-pair cable and high-volume data transmissions at high speed
enable construction of a wide range of networks, from low level systems to high. The link between attached
devices and the network is achieved by an OMRON Controller Link NSB (PCI and ISA) and FinsGateway
Version 3. Refer to the Controller Link operation manual for further details on installation.
CS/CJ/CP-Series PLCs support the wired Controller Link and the new optical Controller Link network.
Use the following procedure to configure Controller Link.
1, 2, 3…
1. Ensure the Network Type is Controller Link.
Summary of Contents for CX-Programmer 9
Page 1: ...Cat No W446 E1 10 CX Programmer Ver 9 SYSMAC WS02 CXPC_ V9 OPERATION MANUAL...
Page 2: ......
Page 3: ...SYSMAC WS02 CXPC V9 CX Programmer Ver 9 Operation Manual Revised December 2009...
Page 4: ......
Page 6: ......
Page 19: ...CX Programmer_Page xvi Unit Versions and Lot Numbers...
Page 30: ......
Page 31: ...PART 1 CX Programmer...
Page 32: ......
Page 100: ......
Page 120: ......
Page 198: ...PART 1 CX Programmer CHAPTER 4 Reference OMRON CX Programmer _Page 118...
Page 224: ...PART 1 CX Programmer Keyboard Shortcuts CX Programmer OMRON CX Programmer _Page 144...
Page 240: ......
Page 241: ...PART 2 CX Server PLC Tools...
Page 242: ......
Page 250: ......
Page 256: ......
Page 268: ...PART 2 CX Server PLC Tools CHAPTER 2 PLC Memory Component OMRON CX Server PLC Tools_Page 18...
Page 286: ......
Page 338: ......
Page 382: ......
Page 414: ......
Page 430: ......
Page 436: ......
Page 437: ...PART 3 CX Server Runtime...
Page 438: ......
Page 482: ......
Page 488: ......
Page 504: ......
Page 530: ......
Page 540: ......
Page 541: ......
Page 542: ......