O
PERATION
:
C
ONFIGURATION
M
ODE
part
3
47
Output 1
cont.
Display
Action
Response
If
"
AUTO TUNE PID
"
was
"
DISABLED
"
, the display will show the following three
submenus so the user may manually enter values for Proportional, Reset and Rate
terms corresponding to P, I, and D. It also can be used for auto PID for disabling
unwanted parameters e. g. PI, enter 0000 for rate:
PROPORTIONAL BAND SUBMENU:
Press ENTER
28) Display flashes 1st digit of the previous P
"
Proportional Band
"
value.
Press MAX & MIN
29) Press MAX and MIN buttons to enter a new
"
Proportional Band
"
value.
Press ENTER
30) Display flashes
"
strd
"
message and advances to
"
Reset Setup
"
submenu.
NOTE:
Proportional band is in degrees of temperature or counts of process.
RESET SETUP SUBMENU:
Press ENTER
31) Display flashes 1st digit of the previous I
"
Reset
"
value.
Press MAX & MIN
32) Press MAX and MIN buttons to enter a new
"
Reset
"
value.
Press ENTER
33) Display flashes
"
strd
"
message and advances to
"
Rate Setup
"
menu.
NOTE:
Reset unit is in seconds 0-3999.
RATE SETUP SUBMENU:
Press ENTER
34) Display flashes 1st digit of previous D
"
Rate
"
value.
Press MAX & MIN
35) Press MAX and MIN buttons to enter a new
"
Rate
"
value.
Press ENTER
36) Display flashes
"
strd
"
message and advances to the
"
Cycle Time
"
submenu for
RTD and Thermocouple types.
If the Output 1 is analog option the display skips
to
"
Damping Factor
"
.
NOTE:
Rate unit is in seconds 000.0-399.9.
RATE
STUP
REST
STUP
PROP
BAND
Summary of Contents for MICROMEGA CN77000 series
Page 4: ...NOTES ...
Page 19: ...SETUP part 2 11 Dip Switch Settings ...
Page 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Page 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Page 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Page 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Page 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Page 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...