Output 1
cont.
Display
Action
Response
The
"
Dead Band
"
submenu will only appear if the
"
On/Off
"
was selected from the
"
Control Type
"
menu.
DEADBAND SUBMENU:
Press ENTER
43) Display flashes 1st digit of the previous
"
Dead Band
"
value.
Press MAX & MIN
44) Press MAX and MIN buttons to enter a new
"
Dead Band
"
value
Press ENTER
45) Display flashes
"
strd
"
message and advances to the
"
Output 2
"
menu.
Dead Band units are the degree of temperature or counts of process.
The Dead Band or neutral zone is the number of degrees or counts (if input type is process) around the setpoint which the
process variable must pass above or below the setpoint, before the output changes state.
DEAD
006.7
DEAD
BAND
Note
☞
Note
☞