56
Output 2
cont.
Display
Action
Response
The
"
Dead Band
"
submenu will only appear if the
"
On/Off
"
was selected from the
"
Control Type
"
menu.
DEAD BAND SUBMENU:
Press ENTER
18) Display flashes 1st digit of the previous
"
Dead Band
"
value.
Press MAX & MIN
19) Press MAX and MIN buttons to enter a new
"
Dead Band
"
value.
Press ENTER
20) Display flashes
"
stored
"
message and advances to the
"
Ramp Value
"
menu.
Refer to Dead Band submenu of Output 1 Menu.
The Dead Band is the number of degrees or counts around the setpoint which the process variable must pass through
before the output changes state.
DEAD
006.7
DEAD
BAND