Command Formats
cont.
Time Proportional: OUT1CNFG.0
= 0 On/off
Analog Proportional:
OUT1CNFG.6 = 0
0 - 20 mA
1 PID
1
4 - 20 mA
OUT1CNFG.1
= 0 Reverse
OUT1CNFG.2
= 0 Auto PID Disable
OUT1CNFG.3
= 0 Adaptive Disable
1 Direct
1 Auto PID Enable
1 Adaptive Enable
OUT1CNFG.4
= 0 Anti Wind Up Disable
OUT1CNFG.5
= 0 Auto PID Stop
1 Anti Wind Up Enable
1 Auto PID Start
Example:
Set PID, Direct, Auto PID Enable, Adaptive Enable, Anti Integral Disable, Auto PID Start. The command data is
00101111Bin = 2FHex. Send *W0C17.