part
3
85
Command Formats
cont.
RDGOFF.0~19
= Offset Data
RDGOFF.20~22
= DP+2
RDGOFF.23
= 0 Positive Offset
1 Negative Offset
RDGSC.0~18
= Scale Data
RDGSC.19
= 0 Direct Scale
RDGSC.20~23
= DP+1
1 Reverse Scale
Example:
To have an input of 4 to 20 mA displayed as 0 to 100,
The Low input value = min. input value * conversion number = 4(mA) x 500 = 2000
The High input value = max. input vlaue * conversion number = 20(mA) x 500 = 10000 (9999)
where: converison number is a coefficient of conversion between input values and real display range.