Alarm 1
cont.
Display
Action
Response
ALARM LATCHED OR UNLATCHED SUBMENU:
Press MAX
7) Display flashes previous selection. Press MAX to
Latched
or
Unlatched
.
Press ENTER
8) Display flashes
"
strd
"
message and advances to
"
Contact Closure
"
submenu.
CONTACT CLOSURE SUBMENU:
Press MAX
9) Display flashes previous selection.
Press MAX to
Normally Closed (
n.c.
)
or
Normally Open (
n.o.
)
.
Press ENTER
10) Display flashes
"
strd
"
message only if it was changed, otherwise press MENU to
advance to
"
Alarm 1 SetupÓ submenu.
ALARM 1 SETUP SUBMENU:
Press MAX
13) Display flashes previous selection. Press MAX to scroll through the available
selections:
Above, Below, HI/Low
and
Band
(Band is active if
"
Deviation
"
was
selected).
Press ENTER
14) Display flashes
"
strd
"
message only if it was changed, otherwise press MENU to
advance to
"
Alarm 1 Low Value
"
submenu.
Above:
Alarm 1 condition triggered when the process variable is greater than the Alarm
Hi Value
. (Lo value ignored)
Below:
Alarm 1 condition triggered when the process variable is less than the Alarm
Low Value
. (Hi value ignored)
Hi/Low:
Alarm 1 condition triggered when the process variable is less than the Alarm
Low Value
or above the
Hi Value
.
Band:
Alarm 1 condition triggered when the process variable is above or below the
"
Band
"
set around Setpoint 1. Band equals
Hi Value
(Lo Value ignored). A
"
Band
"
is set around the Setpoint 1 by the controller only in the
"
Deviation
"
Mode.
ALR.1
ABoV
ALR.1
N.o.
ALR.1
LTCH
part
3
O
PERATION
:
C
ONFIGURATION
M
ODE
34
Summary of Contents for MICROMEGA CN77000 series
Page 4: ...NOTES ...
Page 19: ...SETUP part 2 11 Dip Switch Settings ...
Page 31: ...Figure 3 2 Flowchart for Input Type OPERATION CONFIGURATION MODE part 3 23 ...
Page 36: ...Figure 3 3 Flowchart for Reading Configuration part 3 OPERATION CONFIGURATION MODE 28 ...
Page 45: ...Figure 3 5 Flowchart for Loop Break OPERATION CONFIGURATION MODE part 3 37 ...
Page 49: ...OPERATION CONFIGURATION MODE part 3 41 Figure 3 6 Flowchart for Output 1 ...
Page 59: ...OPERATION CONFIGURATION MODE part 3 51 Figure 3 7 Flowchart for Output 2 ...
Page 65: ...OPERATION CONFIGURATION MODE part 3 57 Figure 3 8 Flowchart for Ramp Soak ...